SL 200 Disconnector Link

A8310-00The SL 200 is a Single Phase in-line Disconnector designed for MV Outdoor overhead  Distribution Systems

Rated Voltage: 36kV
Rated Current: 800A & 1000A
Short Time Withstand Current: 20kA for 3 seconds and  25kA for 1 second, respectively
BIL: 200kVp
Insulator:
Tension - 70kN
Torsion - 47Nm
The SL200 suspension link is used for disconnection duty for :

  • Repairs
  • Temporary connections or disconnections
  • Transformers, overhead to underground transitions, reclosers, sectionalisers and load break switches
  • Limited mounting space for crossarm links
  •  

     

     

    dsc00003-sl200

     

     

    slb-inst-01
    Typical Installation of Recloser/LBS with Disconnector links + Tee Off Links

     

     

    The SL200 disconnector link can be connected directly to the line, or if the connections are required to be line isolated, as in the picture above, terminal palms are provided for the isolated connections.

    Line hooks are available to sling the disconnector on to an existing line. The line is cut after line terminations are completed.

    The disconnector link is operated with an industry standard hook stick

     

    Complies with AS62271.102.2005 and IEC 62271.102 standards

    See also: SLB Tee Off Link for suspension Tee connections

    Downloads:

    Datasheet
    Link, Disconnector , Single Phase, Suspended, type SL200
    Manual
    Specifications
    GA Drawing