Distribution Automation

sspgs Load Break Switch Padmount

The SSPGS Load Break Switch is a padmount fully deadfront switch for underground power distribution systems up to 25.8kV and 630A.

 

For safe and fast operation the design combines puffer load break switches and vacuum fault interrupters, as well as earth switches for every switch combination.

Every bushing can be fitted with a set of current transformers and voltage sensors (-INT option), so all electrical values of the connected distribution system can be measured. The switch can also be remotely operated from system control rooms if it is fitted with SCADA-mate control (based on SEL-551 or SEL-501-2 relay) and RTU. 

 

 

 

Options:
SSPGS- INT
Every bushing in SSPGS- INT Pad Mounted Load Break Switch has a current transformer and voltage sensor, so most electrical values of connected distribution system can be measured. If the optional SCADA-mate control and RTU unit is used, this switchgear can be operated from a system control centre

SSPGS-MANUAL
The SSPGS-MANUAL Pad Mounted Load Break Switch operates manually without any control unit and any power supply.


Safety

  • Field Proven Vacuum Interrupters ensure safe switch operations and fault levels
  • Deadfront design and mechanical cross interlocks between main and earth switches

Reliability

  • Field Proven Vacuum Interrupters ensure long operating life
  • Unique Field Proven Puffer plus Heavy duty Tulip-Shaped Contacts with arc resistant Cu-W tips ensure a short arc-extinguishing time of less than 0.5 cycles at more than 400 times load current
  • The control circuit is powered by an internal power source through an integrated capacitor-potential transformer combination
  • Three phase group-operated mechanism delivers a consistent switching speed regardless of operating speed or method (manual or electrical)
  • Front ground circuit bushings for easy cable access, installation and testing
  • SF6 Gas Insulation enclosed in lifetime sealed stainless steel tank. Less than 0.2% leakage rate per year, with normal insulation and interruption performance even at atmospheric gas pressure
  • Fault interrupter Spring charge mechanism ensures rapid Open-Close-Open performance

Electrical Characteristics

Description SSPGS-16
SSPGS -26
Maximum System Voltage 15 Kv 25.8 kV
Rated Continuous Current 630 A 630 A
ERated Fault Making Current (peak) 52 kAp 32.5 kAp
Electrical Operating Time (Close/Open) 700 ms each 700 ms each
Number of Mechanical Operations (main)
Number of Mechanical Operations(ground)

5,000 times
1,000 times

5,000 times
1,000 times
Short Time Withstand Current ( rms) 20 kA (4 sec) 12.5 kA (3sec)
Breaking
Capacity
Mainly Active Load Current 630 A 630 A
Cable Charging Current Breaking 25 A 25 A
Magnetizing Current Breaking 21 A 21 A
Line Charging Current Breaking 1.5 A 1.5 A
Closed Loop Breaking Current 630 A 630 A
Insulation
Level
Lightning Impulse Withstand Voltage 95 kV BIL 125 kV BIL
Power Frequency Withstand Voltage 50 kV 60 kV
DC Voltage Withstand Voltage 53 kV 78 kV
Weight without Outer Enclosure ( 4 way) 600 Kg ( INT type)
Weight without Outer Enclosure ( 4 way) 350 Kg ( MANUAL type)

The SSPGS Series pad mounted load break switch has been fully certified in accordance with IEC 60265-1 and ANSI/IEEE C37.71 (1984)

Shinsung Product Page